松下4点单元继电器AY33001,RT3S-12V
电源电压:12V
全新原装松下4点单元继电器AY33001,RT3S-12V
松下4点单元继电器AY33001,RT3S-12V
的详细介绍
松下4点单元继电器AY33001,RT3S-12V
1. Input ratings (per PA relay)
Part No.
|
Rated input voltage
|
Input current
(at rated input voltage, 20°C 68℉) (approx.)
|
Allowable variation of rated input voltage
(-20 to +55°C - 4 to +131℉)
|
RT3S-12V
|
12 V DC
|
11.5 mA (Relay 10 mA + LED 1.5 mA)
|
12 V DC ± 10%
|
RT3S-24V
|
24 V DC
|
10.5 mA (Relay 7.5 mA + LED 3 mA)
|
24 V DC ± 10%
|
RT-3 Unit relay/4-point Terminal
Item
|
Specifications
|
Condition
|
Breakdown voltage
|
Between input and output
|
2,000 Vrms
|
for 1 min.
|
Between different terminals (between relays, both ways)
|
1,500 Vrms
|
for 1 min.
|
Insulation resistance
|
Min. 100 MΩ (Measurement at same location as “Breakdown voltage” section.)
|
Using 500 V DC megger
|
Vibration resistance (destructive)
|
10 to 55 Hz at double amplitude
1 mm .039 inch
|
In vertical, horizontal and longitudinal directions
|
Vibration resistance (functional)
|
10 to 55 Hz at double amplitude
1 mm .039 inch
|
|
Shock resistance (destructive)
|
Min. 196 m/s2
|
In vertical, horizontal and longitudinal directions
|
Shock resistance (functional)
|
Min. 98 m/s2
|
In vertical, horizontal and longitudinal directions
|
Ambient temperature
|
-20°C to +55°C - 4°F to +131°F
|
Not freezing and condensing
|
Ambient humidity
|
35% to 85% R.H.
|
Not condensing
|
Storage temperature
|
-30°C to +80°C -22°F to +176°F
|
Not freezing and condensing
|
Terminal screw fasten torque
|
0.3 to 0.5 Nm
|
|
Coil surge absorber
|
Diode (1 A, 400 V)
|
|
Cross connection protecting diode
|
1 A, inverse voltage 400 V
|
|
Unit weight
|
Approx. 100 g 3.53 oz
|
|
*1
|
The value of breakdown voltage and insulation resistance is the initial one.
|
*2
|
Condensing occurs when the unit relay is exposed to sudden temperature change in a high temperature and high humidity atmosphere. This may cause some troubles like insulation failure of the socket or the print circuit board. Take care under this condition.
|
*3
|
Below 0°C 32°F, condensing water can freeze and cause socket contact failures and other problems. Take care under this condition.
|